This the multi-page printable view of this section. Click here to print.

Return to the regular view of this page.

MV Cable Accessory Research

Evaluation of 35-kV terminations

Medium Voltage (MV) cable accessories are used to terminate, join, or connect power cable and to manage electrical stresses. One challenge faced by utilities is assuring the reliability and maximizing the expected life of these components. EPRI has research underway to raise industry understanding and awareness of the function of cable accessories, and to illustrate the impact of various workmanship approaches on the anticipated performance of cable accessories as determined by the presence of partial discharge (PD).

This section describes a multi-year project investigating the performance of medium,voltage (MV) cable terminations. The function of a cable termination is to provide stress control at the cable shield terminus and separation between the cable shield and exposed conductor for external leakage insulation. In order for cable terminations to effectively control electrical stresses, they must be designed to do so at expected operating voltages, and built meticulously to specifications, as minor differences in workmanship may influence-electrical stress control efficacy. Some utilities have experienced in service failures of cable terminations operating at 35kV, and forensic examination has shown that termination designs and preparation practices may have been contributors. In this research, EPRI has performed research to better understand the contributors to in-service failures of MV terminations, and to understand and illustrate the impact of various workmanship approaches on the anticipated health of cable terminations, as determined by the presence of partial discharge (PD). The research was focused on 35 kV cable terminations, as higher operating voltages exacerbate the internal breakdown that will occur with the presence of partial discharge. Both heat shrink and cold shrink termination kits were examined. The cable type utilized for study was a 750 Al XLPE insulated cable with a strippable semiconducting insulation shield

Here is an update video describing MV Cable termination testing underway at EPRI’s Lenox Laboratory.

3002016384: MV Cable Accessory Research: 35-kV Termination Investigation

3002018965: MV Cable Accessory Research: 2020

3002021661: Medium Voltage (MV) Cable Accessory Research: 2021

3002024695: Cable Accessory Research: 2022

1 - Project Overview

Introduction

Utility companies that own and operate urban underground distribution systems face a number of challenges. Installing, assessing and maintaining underground infrastructure is challenging due to its accessibility. Additionally, installed underground distribution infrastructure is aging, and much of the early installed plant is reaching the end of its useful life. Utility managers are charged with managing costs, improving system reliability and resiliency, increasing power throughput, and ensuring the health and safety of workers and the public. In addition, significant changes to electric distribution systems are underway, including the application new load types, new distributed generation sources, new underground equipment and materials, and automation technologies. At the same time, many utilities are facing loss of institutional knowledge. EPRI’s Underground Assets research project focuses on providing utilities the knowledge to acquire, optimize, and maintain underground distribution infrastructure.

One challenge faced by urban underground utilities is assuring the reliability and maximizing the expected life of key asset types such as cable accessories, devices used to terminate, join, or connect power cable and to manage electrical stresses. Beginning in 2019, EPRI has focused its research on 35 kV cable terminations, used to connect underground cable systems with overhead busbar, conductor, or apparatus.

The function of a cable termination is to provide stress control at the cable shield terminus and separation between the cable shield and exposed conductor for external leakage insulation [1]. In order for cable terminations to effectively control electrical stresses, they must, of course, be designed to do so at expected operating voltages, and built meticulously to specifications, as minor differences in workmanship may influence electrical stress control efficacy. Some utilities have experienced in service failures of cable terminations operating at 35kV, and forensic examination has shown that termination designs and preparation practices may have been contributors.

Project Objectives

This research project seeks to raise industry understanding and awareness of the function of cable accessories, and to illustrate the impact of various workmanship approaches on the anticipated performance of cable accessories as determined by the presence of partial discharge (PD). The research is focused on 35 kV terminations, and includes:

  • Examination of field aged cable terminations
  • Examination of newly prepared cable terminations, with and without known defects

The research has been focused on 35 kV cable terminations, as higher operating voltages exacerbate the internal breakdown that will occur with the presence of partial discharge. Both heat shrink and cold shrink termination kits were examined. The cable type utilized for study was a 750 Al XLPE insulated cable with a strippable semiconducting insulation shield.

EPRI’s focus in examining newly prepared terminations was to vary the approach to cutting back the insulation shield and to applying stress relief materials (such as mastic tapes) at this cut back location, as this is a key area of the termination where electrical stressed must be properly managed.

Research Approach

Examination of Field Aged cable terminations

EPRI performed forensic analysis of aged medium voltage cable terminations that had been in service in the field. This included terminations which performed successfully, and those which were removed because of performance issues, such as the presence of partial discharge (PD) identified through testing. The purpose was to examine the factors which contribute to the presence of PD in aged cable terminations to inform specifications and work methods.

EPRI measured the levels of partial discharge present in each sample, including the PD inception and the PD extinction voltage levels. EPRI then dissected each sample to examine termination materials, construction, condition, and workmanship to identify potential causes of PD and to inform specifications and work methods.

Examination of Newly Prepared Cable Terminations

EPRI examined two types of 35-kV terminations, one heat shrink and one cold shrink, built according to manufacturer instructions, while using different work methods to prepare the cut back of the strippable semi-conducting insulation shield, and varying the placement of tapes / mastics provided by the manufacturer and applied to the insulation shield cutback location.

EPRI measured the levels of partial discharge present in each sample, including the PD inception and the PD extinction voltage levels, seeking to better understand how various preparation approaches affect the levels of PD measured in completed terminations.

Preparation of Terminations to be tested

Termination samples were prepared as follows:

  • For both the Heat Shrink and Cold Shrink Terminations, the insulation shield “edge” was prepared using:

    • Knife cut (Knife Cut)

    • Cutting Tool cut, creating a square edge (Square Cut)

    • Chamfered Cut

  • For heat shrink terminations, the placement of stress reducing mastic tapes was varied to reflect conflicting interpretations of preparation instructions.

    • Tape centered half over the insulation and half over the semi con insulation shield (Tape Centered)

    • Tape filling in the edge or corner, and then wrapped centered over the insulation and semi con insulation shield (Tape Filled)

  • For cold shrink terminations, for one sample (with a Knife Cut), EPRI varied the placement of the tube such that the placement of the mastic (within the tube) was varied.

In all, ten (10) 35-kV terminations were prepared for testing.

2 - Terminations Assembled using Varied Work Practices

Overview

One driver of EPRI’s research into the performance of cable terminations is the experience of cable termination failures by some utilities. One utility, who had experienced four in-service failures of newly installed 35kV cable terminations, performed partial discharge (PD) testing of installed cables through a service provider. These tests confirmed PD with a magnitude of concern in many of the companion terminations. Forensic analysis of two of the field failures by the utility company indicated that the cables failed near the insulation shield cutback area of each assembled termination. A group of eighteen (18) terminations were removed from service for testing and root cause evaluation by EPRI. PD testing at the EPRI facility in Lenox, MA confirmed that many of these terminations were exhibiting a significant level of internal PD activity. Not all terminations could be evaluated in this manner due to limited cable length at the free end. Of those that could be tested, all exhibited PD at a level well above the reasonably accepted value of 5 pC (picocoulombs of apparent charge). Subsequent dissections of the 18 terminations removed from service revealed that the electric stress control measures were inconsistently implemented for a number of reasons including unclear instructions from the termination manufacturers, lack of fundamental technical reference information, work practice concerns, and significant installation constraints including tight bends and poor access for termination installation. In addition, there was limited familiarity with the particular cable and terminations. Similar problems were found with three cold-shrink terminations that were assembled for evaluation as an alternate. A synopsis of the forensic analyses is presented in the following section.

To provide a fundamental basis for understanding the role of work practices, termination designs, and assembly methods, a series of cable terminations were assembled with varied work practices and subjected to electrical testing, with particular emphasis on the occurrence of PD and, where detected, on the magnitude and characteristics of the PD activity. It is this effort that is the focus of this section.

Synopsis of Field Failures and Termination Partial Discharge Activity

A large number of cable terminations were installed at a facility that was being upgraded. The affected cables included two distinct groups. One group included cable rated for 46 kV service, energized at 34 kV, with a 4/0 stranded aluminum conductor, insulated with tree-retardant crosslinked polyethylene (TRXLPE) applied to the 133 % level [2]. The conductor strands include a dual technology water-blocking treatment. The second set of cable is rated for 35 kV service and also energized at 34 kV. These include a 750 MCM stranded aluminum conductor with the same strand block technology, TRXLPE insulation at the 100 % insulation level, and stranded copper concentric neutral conductors. Both types of cable were manufactured by the same supplier. Both designs include a strippable insulation shield and jacketed construction. Figure 1 and Figure 2 present overviews of the heat-shrink and cold-shrink terminations removed from service and submitted for analysis.

Figure 1: Overview of selected heat-shrink terminations removed from service
Figure 2: Overview of cold-shrink terminations assembled for testing

PD Testing following Termination Removal

Partial discharge testing was planned for the set of 18 samples removed from service specifically for investigative purposes. Due to limited spare length on the affected cable circuits, some the samples were provided with attached cable lengths too short to support application of stress control terminations, essential for such testing. Where the lengths were suitable for installation of manually applied tape type terminations, these were installed to support PD testing. This group included 12 of the 18 terminations. It should be noted that all of these terminations had been subjected to testing for PD in the field prior to being removed from service. The high PD values measured provided a basis for their removal.

PD testing of the 12 samples indicated PD inception at a level below phase-to-ground potential. This indicated that the cables and corresponding terminations would have been operating under conditions with damaging internal electrical discharges. These tests indicated a general problem as opposed to an isolated cause, limited to a small fraction of the population.

PD initiation below service voltage was also measured in 2 of the 3 cold shrink terminations. One of these had been dissected and could not be tested. Forensic analysis suggested that this termination would also have exhibited PD at or below service voltage.

The PD testing method and cable preparation method for this testing are described in a following section.

Forensic Examination Summary

Following PD testing, all of the termination samples were dissected and examined for a review of the assembly details, degradation or defects, electrical damage, physical damage, or any other anomalies that might be causative of the measured PD. Eighteen terminations were recovered from service and three additional terminations, assembled by the same crews using the same type of cable, were also provided for teardowns and PD root cause evaluation. The terminations recovered from service were designed with heat-shrinkable technology. The three independent terminations were designed with cold-shrink technology. None of the latter three had ever been energized.

All of the terminations recovered from service were systematically dissected for examination of the internal components and assembly practices, following PD testing, where possible. In each of the previously-installed terminations, defects were found at the insulation shield cutback. In some cases, the cutbacks were made reasonably well, but the heat-shrinkable termination stress control material did not flow into and fill the entire lower corner of the shield cutback where it intersects the insulation. An example is shown in Figure 3. In this example, the shield cutback exhibits some edge scalloping and exposed insulation can be seen at the base of the vertical face of the cutback. Additional examples of this prevalent condition are shown in Figure 4 and Figure 5, corresponding to the heat-shrink terminations. Exposure of the insulation at this location inevitably leads to PD.

The same problem was found when the cold-shrink terminations were dissected. In each case, the stress control putty material did not fully conform to and fill the corner at the base of the insulation shield cutback. An example from one the terminations is presented in Figure 6.

Complete filling of this interface with the shielding material is made more complicated when the insulation shield cutback is not produced in a uniform manner, without asperities, projections, and cuts into the adjacent insulation. The assembly instructions draw superficial attention to the details at this location and do not address the cable insulation surface preparation at all. This includes insulation sanding requirements, cleaning, and inspection. No detailed instructions are provided regarding selection and use of insulation shield cutback tools. No direction is provided about the ideal geometry for this interface. This is the most highly stressed area of the cable-to-termination interface. All 18 of the heat-shrink terminations were affected by insufficient shielding at the insulation shield cutback. The same problem was found in all 3 of the cold-shrink terminations.

Figure 3: Example of insulation exposed at base of insulation shield cutback in heat-shrink termination
Figure 4: Additional example of insulation exposure at insulation shield cutback base in heat-shrink termination
Figure 5: Third example of insulation exposure at base of insulation shield cutback in heat-shrink termination
Figure 6: Insulation exposure and ragged edge of insulation shield cutback in cold-shrink termination

Research Sample Production

Following the findings from examination of the terminations removed from service, a study was undertaken to explore the role of cable preparation methods for elimination of partial discharge at the insulation shield cutback. Various field practices were reviewed and practical options for preparation of this interface were considered. These approaches were adopted as a basis for assembly and subsequent testing of terminations that represent a range of insulation shield cutback profiles and shielding material effectiveness. Heat-shrink and cold-shrink terminations were prepared for these tests. The cable type used for this matrix of test samples included the same cable used by the utility company. This includes a TRXLPE insulation system and a strippable insulation shield, as previously described.

Field crew members from a member utility company assisted EPRI with preparation of the terminations for study. Cables staged for these assemblies are shown in Figure 7. The terminations were prepared by varying the type of edge profile formed when cutting back the strippable insulation shield, the position of stress control tapes or mastics provided by the manufacturer, and the method of stress control material application to the insulation shield cutback area.

Figure 7: Preparation of cable termination samples

EPRI utilized three different approaches for varying the type of ‘edge’ used when cutting back the insulation shield. These included a ‘knife’ cut, using a standard lineman’s knife as shown in Figure 8 and Figure 9; a ‘square’ cut, using a tool designed for scoring the semiconducting insulation shield layer, as shown in Figure 10 and Figure 11; and a ‘chamfered’ cut prepared with a rat-tail file, as shown in Figure 12 and Figure 13. A guide was improvised for the rat-tail file by application of a stainless steel constant force spring band, as used to joined braided ground conductors to tape type neutral shields. The file is shown resting against the spring.

Figure 8: ‘Knife cut’ of semiconducting shield layer using a lineman’s knife
Figure 9: ‘Knife cut’ of semiconducting shield layer using a lineman’s knife
Figure 10: ‘Square cut’ of semiconducting shield layer using a scoring tool
Figure 11: ‘Square cut’ of semiconducting shield layer using a scoring tool
Figure 12: ‘Chamfered cut’ of semiconducting shield layer using a rat-tail file
Figure 13: ‘Chamfered cut’ of semiconducting shield layer using a rat-tail file

EPRI also varied the approach used to apply the stress relieving mastic (SRM) tapes provided with the termination kits. One approach, identified as ‘tape centered’, was to center the tape over the insulation shield cutback, with one half the tape covering the insulation and the other half covering the semiconducting shield layer as shown in Figure 14. This approach has the potential to create a void at the insulation shield cutback location.

Figure 14: Tape centered – completed wrap of tape centered over semicon layer and insulation

Another approach, identified as ‘tape filled’, included abutting the tape to the insulation shield layer cutback edge and completing one wrap onto the insulation surface with the tape filling in the edge or corner, and then completing the application of the tape by centering over the insulation and insulation shield as shown in Figure 15 and Figure 16.

Figure 15: Tape filled – starting one complete wrap of the tape applied to insulation
Figure 16: Tape filled – completing one wrap of the tape applied to insulation

With the cold-shrink termination design, the stress relief mastic material is pre-positioned and bonded to the inner surface of the shielded insulation tube, so that the use of an SRM tape is not required. The proper application of the shrink tube depends on the placement of the tube and a cutback of the semi conducting layer that conforms to manufacturer requirements. Using one of the knife cut samples, EPRI varied the placement of the shrink tube by one inch, such that the mastic would be improperly applied. Figure 17 shows the cold-shrink termination being positioned over the cable, prior to removal of the internal expansion mandrel.

Figure 17: Cold shrink termination, ‘knife’ cut, improperly placed tube

For all of these samples, the insulation surface was not sanded overall. Localized sanding was applied only where there were visible indications of semiconducting material remaining on the insulation surface. All of the termination samples were prepared with 18 in. (46 cm) of cable extending from the base for subsequent application of testing terminations. In all, ten (10) 35-kV cable terminations samples were prepared for testing. A summary description of these samples is presented in Table 1.

Table 1: Summary description of test samples prepared to explore assembly variables
Sample ID Cable Preparation Termination Type
A Tool-cut square insulation shield cutback, stress control tape centered over cutback Heat-shrink
B Tool-cut square insulation shield cutback, tape-filled Heat-shrink
C Knife-cut insulation shield cutback, stress control tape centered over gap Heat-shrink
D Chamfered insulation shield profile, stress control tape centered over cutback Heat-shrink
E Knife-cut insulation shield cutback, properly placed tube Cold-shrink
F Tool-cut square insulation shield cutback, tube properly positioned Cold-shrink
G Knife-cut insulation shield cutback, tube offset 1 inch from lug end Cold-shrink
H Chamfered insulation shield cutback, stress control tape-filled Heat-shrink
I Knife cutback of insulation shield, tape-filled cutback edge Heat-shrink
J Chamfered insulation shield cutback, tube properly positioned Cold-shrink

Cable Termination Application

Manually-applied terminations were installed onto the bare cable end of each of the cable samples to support partial discharge testing. The cables were prepared by removal of the jacket with a jacket-stripping tool. The insulation was then stripped mechanically after preparing a circumferential ring cut with a corresponding specialized tool. Axial cuts were made through the surface of the insulation shield, then this was peeled away. In all cases, the insulation shield terminus was chamfered in stages, beginning with a utility knife to make a series of angled cuts to achieve a long, shallow beveled profile. Next, the insulation and beveled insulation shield terminus were sanded with 120 grit cloth-backed aluminum oxide abrasive to achieve a uniform insulation surface and smooth beveled edge. The edge was carefully tapered to achieve the thinnest transition possible. This is shown in Figure 18. Semiconducting tape was applied over the tapered shield profile, extending just over the edge onto the insulation to establish a uniform, straight terminal edge. Application of the stress control tape is shown in Figure 19. Next, insulating tape was applied carefully abutting the semiconducting tape, and, by application of many layers in a controlled manner, a conical profile was developed over the insulation until the diameter of the cable was approximately doubled. Following this, a layer of semiconducting tape was wrapped, beginning with an overlap of the insulation shield and first layer of semiconducting tape. Wraps continued until the tape reach the apex of the cone, thus forming a divergent insulation shield profile. Insulating tape was then wrapped over this assembly to build the insulation thickness against discharge into the surrounding air. Technical references for assembly of hand-made terminations can be found in the public domain [13]. A completed termination on a cable undergoing high voltage PD testing is shown in Figure 20.

Figure 18: Tapered profile prepared at edge of insulation shield cutback
Figure 19: Application of semiconducting stress control tape at tapered end of shield cutback
Figure 20: Cable with handmade termination undergoing high voltage PD testing

Partial Discharge Testing Methods

Termination samples were subjected to PD testing using laboratory conditions and equipment. The samples were energized to 34 kV service voltage level, using a line-to-ground voltage of approximately 19.7 kV. To maintain a discharge-free test, the high voltage lead wire was shielded with a large corrugated metal tube. The free end of the cable was terminated with a corona ring, attached directly to the conductor with a threaded bolt connection. The outer diameter of the corona ring used for these tests is 18 in. (46 cm). A test sample with these shielded connections in shown in Figure 20.

The samples were energized using a special, low noise, variable ac power supply, equipped with a voltage regulator. The transformer includes a low noise porcelain bushing fitted with a corona ring at the output terminal. The high voltage terminal was connected in parallel to an instrumentation-grade capacitive voltage divider. This equipment is shown in Figure 21.

PD measurement was made using an Omicron detection system and digital bandpass filter network coupled to the voltage divider. Omicron analysis software was used to record and analyze PD measurements from the samples. A computer showing the Omicron analysis screen is presented in Figure 22.

Figure 21: Test set-up for PD detection and measurement
Figure 22: Computer screen showing Omicron PD analysis in progress

Corona Camera Inspections

During development of the PD testing protocols, a corona camera was used to scan the test leads, transformer connections, the hand-applied tape terminations, and the combined cable and termination samples under test. Figure 23 presents an example of a visible light image of a tape termination with a superimposed image of partial discharge signals converted to a visible light signal. The images are synchronized, thus enabling source of corona and sporadic electrical discharge to be identified for analysis or corrective action. In this example, the hand-made terminations were determined to be under-insulated for use at 20 kV. These were subsequently re-insulated and found to pass this inspection. All samples and all of the hand-applied terminations were inspected with a corona camera during the PD testing to ensure that no interference was competing with the measurements.

Figure 23: Example of PD detected on hand-made termination surface

Partial Discharge Testing Results

The termination samples were subjected to phase-to-ground voltage level during testing to determine if PD activity was present. The PD magnitude was then measured and the sample was held at this voltage level for a period of time. Following this, the voltage level was lowered incrementally until the PD activity stopped. This value corresponds to the PD extinction voltage or PDEV. The voltage was then raised again until the first trace of PD activity initiated. This value is identified as the PD inception voltage or PDIV.

Figure 24 presents a screen shot from the PD detection and measurement system, applied to sample C, with PD pulses accumulated during a 10 minute hold at 20 kV. The sine wave corresponding to the applied voltage is superimposed on the accumulated PD distribution. As noted in this display, the PD activity is most prevalent at the ‘zero crossing’ where the applied voltage crosses from negative to positive and back. This is an expected response.

Figure 24: Accumulated PD signal from termination sample C

PD testing was conducted in a set of test designed to initially raise the applied voltage to service level (19.7 - 20 kV), determine if PD is present, then monitor the PD during a 10 minute ‘soak’ period wherein the applied voltage remained constant. The PDIV and PDEV values were measured for each sample three times, with the average values reported. These test results are summarized in Table 2.

Table 2: Summary of PD tests of terminations prepared with various practices and a 10 minute hold
Sample ID Cable Preparation Termination Type PDIV, average, kV initial PD magnitude, average pC PDEV, average, kV

PD at

20.4 kV,

10 minute

soak, pC

Test Comments
A Tool-cut square insulation shield cutback, stress control tape centered over cutback Heat-shrink 17.4 20 - 30 16.5 40 - 50 PD steadily increased in frequency and magnitude during testing
B Tool-cut square insulation shield cutback, tape-filled Heat-shrink -- 10 - 20 --

none

detected

PD extinguished after 4 minutes at voltage
C Knife-cut insulation shield cutback, stress control tape centered over gap Heat-shrink 18.0 10 17.5 -- Occasional PD pulse at 1 minute interval
D Chamfered insulation shield profile, stress control tape centered over cutback Heat-shrink --

none

detected

-- none detected PD extinguished early, could not determine PDIV and PDEV
E Knife-cut insulation shield cutback, properly placed tube Cold-shrink 18.65 10 - 30 18.95 20 - 40 Slow increase in PD magnitude and frequency
F Tool-cut square insulation shield cutback, tube properly positioned Cold-shrink 16.5 10 - 40 16.6 10 - 20 PD persisted throughout the test, but declined slowly.
G Knife-cut insulation shield cutback, tube offset 1 inch from lug end Cold-shrink 17.2 100 - 150 18.2 100 - 150 PD activity level consistent throughout test
H Chamfered insulation shield cutback, , stress control tape-filled Heat-shrink --

none

detected

--

none

detected

No PD detected, even sporadically
I Knife cutback of insulation shield, tape-filled cutback edge Heat-shrink --

none

detected

--

none

detected

No PD activity in test period
J Chamfered insulation shield cutback, termination properly positioned Cold-shrink --

none

detected

--

none

detected

No PD activity in test period

3 - Conclusion

The results from these tests generally followed a logical path. The termination prepared with a gross defect, sample G (cold-shrink tube incorrectly positioned) exhibited a high PD level that was sustained throughout the test period. This would be expected due to the loss of electric stress control at the insulation and insulation shied interface.

The samples prepared with chamfered or tapered insulation shield edges (samples D, H, and J) were found to have no detectable PD activity at service voltage, at any point during the testing. This is also expected on the basis of fundamental electric stress control considerations.

The samples that would be expected to feature gaps the insulation and insulation shield interface (Samples A and C) were found to produce PD at the outset. PD persisted in Sample A, but mostly extinguished in Sample C.

Elevated and persistent PD activity was found in the cold-shrink termination samples with a square edge on the insulation shield cutback and the shrink tube correctly positioned (Samples E and F). This finding indicates that the stress control material will not adequately fill this interface, independent of the two cutback methods evaluated. This finding is also consistent with the teardown inspections of three trial cold-shrink terminations.

The absence of PD in Samples B and I at least suggests that stress control tape can be used to fill a square-cut insulation shield end, if applied with attention to detail, combined with a properly prepared cutback.

For those samples where PD is present, it will eventually break down the polymers inside these terminations, though the rate would not be linear. In the early stages, PD-initiated breakdown of the polymers would be expected to produce gaseous decomposition products, most of which would be non-polar (i.e., non-conductive). Gasses of this general nature would accumulate under pressure where voids are present and electrical discharges initiated. The effect of such gases would be to ‘quench’ PD for a period of time that depends on many variables. The effect can be seen by allowing a sample with initial, but declining PD magnitude to ’extinguish’. Sample B was subjected to such testing. Following PD extinction, the same termination was re-energized at various intervals. Only after approximately 24 hours of idle time did the PD reappear. This outcome is expected since gases that form and occupy void space will slowly diffuse through the polymer and escape. Results of this experiment indicate that PD testing would be most effective on circuits that had been off-line or never energized.

Longer-term degradation due to the cumulative effects of PD are inarguably damaging, as shown by many years of research at EPRI. The terminations prepared for this study have been preserved and will be subjected to longer-term testing and research to provide a more comprehensive understanding of the source, detection, and interpretation of PD in cable accessories.

4 - References

  1. EPRI Underground Distribution Systems Reference Book, 2016 Edition. EPRI, Palo Alto, CA: 2020. 3002018091.

  2. Specification CS8-13 for Extruded Dielectric Power Cables Rated 5 through 46 kV, Association of Edison Illuminating Companies, September 2013 and previous.

  3. IEEE 1816-2013 IEEE Guide for Preparation Techniques of Extruded Dielectric, Shielded Cables Rated 2.5 kV through 46 kV and the Installation of Mating Accessories, IEEE, Sept. 2013

  4. IEEE 1493-2006 IEEE Guide for the Evaluation of Solvents Used for Cleaning Electrical Cable and Accessories, IEEE Dec. 2006.

  5. IEEE 1617-2007 IEEE Guide for Detection, Mitigation and Control of Concentric Neutral Corrosion in Medium-Voltage Underground Cables, IEEE, Feb. 2008.

  6. IEEE 48 IEEE Standard for Test Procedures and Requirements for Alternating-Current Cable Terminations Used on Shielded Cables Having Laminated Insulation Rated 2.5 kV through 756 kV or Extruded Insulation Rated 2.5 kV through 500 kV, IEEE, Aug., 2009.

  7. Handbook of Chemistry and Physics, 100th Edition, CRC Press, 2018.

  8. AEIC CG-11 Guide for Reduced Diameter Shielded Power Cables Rated 5 through 46 kV, Association of Edison Illuminating Companies, Sept. 2013 and previous.

  9. Why Are Terminations Required on Shielded Medium Voltage Cables, Technical News, Edition 0016, The Okonite Company, 2004.

  10. Splicing and Terminating of Portable Cables, Form INS-0083-0807, General Cable Technologies Corp., 2007

  11. Power Cable Splicing & Terminating, R. Goodman and W. Osborn, 3M Corp., 2008.

  12. Electric Power Connections for Substations, ANSI/NEMA Standard CC1-2009, National Electrical Manufacturers Association, 2009.

  13. Wire and Cable Selection and Technical Data, Document CM-621, General Electric Corp., Jan. 1964.